Description
Overload Relay SS-30-N440 in Pakistan BR2649
Product Description:
Two of three phase motor currents are monitored by current transformers.External Cts are required for currents more than 60Amps.The internal solid state circuitry compares with the preset current time,the device trips,and changes internal SPDT relay contacts,Red LED remains illuminated indicating an overload trip has occurred.Until manual or remote electrical reset by interrupting supply,is initiated.Specification:
Model |
EOCR-SS | ||
Current range |
05)0.5-5A | ||
30)5-30A | |||
60)5-60A | |||
Over 60A to 800A ,05 fitted w/external CTs | |||
Rated voltage |
440VAC,50/60Hz | ||
Operating setting |
D-TIME | 0.2-30 seconds | |
O-TIME | 0.2-10 seconds | ||
Accuracy |
Current | ±10% | |
Time | ±15% of max.time set value | ||
Time characteristics |
Definite time | ||
Control voltage |
220)Voltage Free (90~260)VAC,50/60Hz 221)440)Voltage Free (1890~480)VAC,50/60Hz Other voltage optional. | ||
Rate Voltage |
600VAC,50/60Hz | ||
Current sensing |
2 CTs | ||
Output contacts |
Contacts |
SPDT 3A/250AVC Resistive | |
Condition |
N Type |
Normally energized:95 - 98close | |
R Type |
Normally de-energized:95 - 98close | ||
Reset |
Manual or remote electrical by interrupting supply | ||
Environment |
Temp. |
Run |
-20~60 deg? |
Store |
-30~80 deg? | ||
Humid |
30~85% RH,non-condensing | ||
Insulation |
Between casing and circuits:Over 10M?with DC 500V megger | ||
Dielectric strength |
1)Between casing and circuits:AC 2000V,60Hz,1min | ||
2)Between contacts: AC 1000V,60Hz,1min | |||
3)Between circuits:AC 2000V,60Hz.1min | |||
Power consumption |
Under 2W | ||
Mounting |
35mm Din Rail(D) or Pane(P) |