DVP06AD-S Delta PLC 6 point 14-bit resolution Analog I/O Module in Pakistan BR1048
The analog signal input module DVP06AD-S is able to receive 6 points of external analog signal inputs (both in voltage and current) and convert the signals into 14-bit digital ones. It is able to read and write the data in the module through FROM/TO instructions given by the program of DVP-PLC SS/SA/SX/SC/SV series MPU. There are 49 16-bit control registers in the module. 2. The user can select voltage or current output by wiring. Range of voltage output: +-10V DC (resolution: 1.25mV). Range of current output: +-20mA (resolution: 5uA).Specifications:
| Analog/Digital (6A/D) module | Voltage input | Current input |
| Power supply voltage | 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%) | |
| Analog input channel | 6 channels/module | |
| Range of analog input | +-10V | +-20mA |
| Range of digital conversion | +-8,000 | +-4,000 |
| Resolution | 14 bits (1LSB=1.25mV) | 13 bits (1LSB=5uA) |
| Input impedance | 200K? or more | 250? |
| Overall accuracy | +-0.5% when in full scale (25°C, 77°F) +-1% when in full scale in the range of 0 ~ 55°C, 32 ~ 131°F | |
| Response time | 3ms × the number of channels | |
| Isolation | Isolation between digital area and analog area. No isolation among channels. | |
| Range of absolute input | +-15V | +-32mA |
| Digital data format | 13 significant bits out of 16 bits are available; in 2’s complement. | |
| Average function | Yes. Available for setting up in CR#2 ~ CR#7; range: K1 ~ K20. | |
| Self-diagnosis | Upper and lower bound detection/channel | |
| Communication mode (RS-485) | ASCII/RTU mode. Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1) RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1) RS-485 cannot be used when connected to PLC MPU in series. | |
| When connected to DVP-PLC MPU in series | The modules are numbered from 0 to 7 automatically by their distance from MPU. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/Opoints. | |
| Max. rated power consumption | 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W, supplied by external power. | |
| Operation/storage | Operation: 0°C ~ 55°C (temperature); 5 ~ 95% (humidity); pollution degree 2. Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity). | |