FBs-6AD BR2338
Input point 6 points Output point ? Input/Output value -8192~8191 or 0~16383 (14-bit) Input/output Signal range Bipolar Voltage: -10~10V or -5~5V Current: -20~20mA or -10~10mA Unipolar Voltage: 0~10V or 0~5V Current: 0~20mA or 0~10mA Maximum resolution Voltage: 0.3mV (5V/16384) Current: 0.61?A (10mA/16384) Accuracy ±1% Conversion time Conversion once for each scan Maximum input signal Input voltage: ±15V Input current: ±30mA Allowable load range ? Input impedance Input voltage: 63.2K? Input current: 250? Isolation method Transformer(power) and photocouple(signal) isolation, 500VAC, 1 minute, no isolation between each channel Power consumptio 24VDC –15%/+20%, 3.2W max. Wiring mechanism 7.62 mm fixed terminal block