Analog/Digital (6A/D) module | Voltage input | Current input |
Power supply voltage | 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%) |
Analog input channel | 6 channels/module |
Range of analog input | +-10V | +-20mA |
Range of digital conversion | +-8,000 | +-4,000 |
Resolution | 14 bits (1LSB=1.25mV) | 13 bits (1LSB=5uA) |
Input impedance | 200K? or more | 250? |
Overall accuracy | +-0.5% when in full scale (25°C, 77°F) +-1% when in full scale in the range of 0 ~ 55°C, 32 ~ 131°F |
Response time | 3ms × the number of channels |
Isolation | Isolation between digital area and analog area. No isolation among channels. |
Range of absolute input | +-15V | +-32mA |
Digital data format | 13 significant bits out of 16 bits are available; in 2’s complement. |
Average function | Yes. Available for setting up in CR#2 ~ CR#7; range: K1 ~ K20. |
Self-diagnosis | Upper and lower bound detection/channel |
Communication mode (RS-485) | ASCII/RTU mode. Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1) RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1) RS-485 cannot be used when connected to PLC MPU in series. |
When connected to DVP-PLC MPU in series | The modules are numbered from 0 to 7 automatically by their distance from MPU. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/Opoints. |
Max. rated power consumption | 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W, supplied by external power. |
Operation/storage | Operation: 0°C ~ 55°C (temperature); 5 ~ 95% (humidity); pollution degree 2. Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity). |